Matt Cornachione

1paper

1 Paper

29.9SYMay 14
Optimizing Chilled Water Systems with Cooling Towers via Virtual Power Metrics and Extremum-Seeking Control

Min Gyung Yu, Alex Vlachokostas, Karthik Devaprasad et al.

This paper presents an extremum seeking control (ESC) method for cooling tower fans to minimize overall power consumption of a chilled water plant system. Simulation studies across different climate locations demonstrate energy savings of approximately 15% compared to conventional control during summer conditions. This paper also proposes a virtual power meter (VPM) to enable use of the strategy in systems that lack physical power meters. Validation tests for the VPMs against physical meters showed good accuracy with a correlation of 96.11% and a normalized error of 5.11%. Coupled with the VPM, the proposed ESC control solution can be implemented on systems using typically available sensor measurements without the need for additional instrumentation.