Safe Reconnection Time for Large-Scale Data Center Loads: An Analytical Framework for Transient Stability Assessment

arXiv:2604.2400944.11 citations
AI Analysis

For power system operators and data center operators, this provides a physics-informed criterion to bound reconnection windows and inform UPS logic, addressing a growing operational challenge from large data center loads.

This paper develops an analytical framework to determine the safe reconnection time for large data center loads after disturbance-induced disconnection, preventing repeated connect-disconnect flapping. The framework uses an energy function method to guarantee post-reconnection stability within operational limits, validated by time-domain simulations.

The rapid growth of large, power-electronics-rich data center (DC) loads is creating new operational challenges for bulk power systems. A key risk arises when a DC uninterruptible power supply (UPS) disconnects the facility during voltage/frequency disturbances and then reconnects it while the bulk grid is still dynamically settling to a new equilibrium point. Poorly timed reconnection can amplify electromechanical oscillations, deepen frequency deviations, and lead to repeated connect-disconnect \emph{flapping}. In this paper, we develop an analytical framework to characterize the \emph{safe reconnection time} for large DC loads after a disturbance-induced disconnection that avoids flapping. Using a model in the spirit of the classical single-machine infinite-bus system, we capture (i) swing dynamics during the disconnection interval and (ii) voltage-angle coupling at the load bus, which determines the electrical power step at reconnection under constant-power load assumptions. Using energy function method, we characterize the critical safe reconnection time such that for any reconnection time after the critical safe reconnection time, the post-reconnection trajectory is guaranteed to remain within operational limits (frequency/angle/voltage) and converge to the post-reconnection equilibrium, thereby preventing flapping. Time-domain simulations validate the effectiveness of the proposed analytical approach. The results provide a simple, physics-informed criterion that can be used to bound reconnection windows for large DC facilities and inform UPS reconnection logic.

Foundations

The foundational work for this paper's niche, ranked by how specifically the neighbourhood builds on it — not by global fame.

Your Notes