Frequency-Domain Compliance Assessment of Grid-Forming Devices

arXiv:2605.0213149.8
AI Analysis

For system operators and regulators, this provides a more accurate and robust method to evaluate GFMI compliance, replacing error-prone time-domain approaches.

This paper proposes a frequency-domain compliance criterion for grid-forming inverters (GFMIs) to assess their voltage-source-behind-impedance (VSBI) characteristic, addressing errors in time-domain methods. The criterion is validated on generic GFMI models and shown to impact small-signal stability in the IEEE 39-bus system.

Grid-ForMing Inverters (GFMIs) are expected to provide voltage stiffness to the grid. Explicitly, system operators (SOs) and regulators expect GFMIs to behave like a "voltage source behind impedance (VSBI)" in the (sub)-transient time frame. SOs assess this VSBI characteristic of GFMIs during compliance by defining a pass-fail time-domain criterion. This is done by evaluating the GFMIs' active (or reactive) power/current response to step changes in voltage phase (and magnitude) at its terminals. However, this approach is prone to errors due to poorly defined measurement specifications for very fast (less than a cycle) transients. To address this, this work proposes a compliance criterion for the VSBI characteristic of GFMIs in the frequency domain based on elements of the frequency-domain Jacobian. The compliance criterion is defined in terms of the minimum expected P(s)/θ(s) and Q(s)/V(s) Bode plot characteristics across a specific frequency range. The equivalence between the time-domain and frequency-domain criteria is established. The proposed method is demonstrated by assessing the compliance of generic NLR (formerly NREL) GFMI models in PSCAD. Furthermore, the impact of GFMI compliance on the small-signal stability of the IEEE 39-bus bulk-power system is demonstrated.

Foundations

The foundational work for this paper's niche, ranked by how specifically the neighbourhood builds on it — not by global fame.

Your Notes