Source Side Mitigation of AI Datacenter Power Fluctuations with a Hybrid Energy Storage System and Residual Differentiable Predictive Control

arXiv:2606.048698.5
Predicted impact top 21% in SY · last 90 daysOriginality Incremental advance
AI Analysis

For grid operators and datacenter operators, this work provides a local solution to mitigate frequency disturbances caused by AI workloads, reducing the need for grid-level interventions.

This paper proposes a hybrid energy storage system with differentiable predictive control (HESS-DPC) to smooth power fluctuations from AI datacenters. Simulations on the NPCC 140-bus system show it reduces generator peak-to-peak frequency deviations by over 80%, with the worst-affected generator dropping from 15.1 mHz to 1.3 mHz.

The rapid growth of hyperscale AI datacenters introduces structured, workload-driven active-power fluctuations at the point of interconnection. These fluctuations appear to the grid as time-varying disturbance injections that cannot be captured by conventional peak- or average-load representations. To reduce the residual power disturbance before it propagates into the bulk power system, this paper proposes a hybrid energy storage system with differentiable predictive control (HESS-DPC) framework for datacenter-side power smoothing. A workload-driven disturbance model is first established, representing the point-of-interconnection load deviation as the superposition of training and fine-tuning workloads to capture the structured forcing inputs that can excite generator frequency dynamics. A frequency-based rule-based controller then allocates this deviation between a battery energy storage system (BESS) and a supercapacitor (SC), assigning the energy-dominant component to the BESS and the fast-varying component to the SC. To overcome the anticipation and constraint limitations of fixed-frequency decomposition, a residual differentiable predictive control policy is trained offline to compute finite-horizon command corrections around the rule-based baseline while enforcing a one-step safeguard. Simulations on the NPCC 140-bus system show that HESS-DPC reduces grid-side residual deviations during workload transitions, improves SC state-of-charge sustainability over extended operation, and reduces generator peak-to-peak frequency deviations by more than 80 percent across all monitored generators, with the worst-affected generator response falling from 15.1 mHz to 1.3 mHz. These results confirm that local active-power smoothing at the datacenter point of interconnection can substantially mitigate frequency disturbances caused by AI workloads.

Foundations

The foundational work for this paper's niche, ranked by how specifically the neighbourhood builds on it — not by global fame.

Your Notes